    Lighting ring main

    Just finished an attic conversion and the electrician has left two cables for a lighting ring dangling next to the consumer unit for connection. I note the twin and earth wire is 1mm2, I thought lighting rings were1.5mm2.

    Is there a minimum requirement?

    0
    0

    Lighting can be wired in both 1.0mm or 1.5mm

    Presuming it has the right protective device - e.g 6 or 10A

    1
    0

    lighting circuits arent usually on a ring, its just one supply from the consumer unit that ends at the last light rather than return to the consumer unit

    im not saying its wrong as im not a spark, but its not the norn to install it as a ring

    1
    0

    Could be two separate radials, rather than a ring.

    0
    0

    http://www.smartbuild.uk.com | Structural Engineer

    bit odd for a loft conversion

    one could be an extractor fan feed maybe?

    0
    0

    google would have told you the answer v quickly!